Learn more by watching our HAGER ADC925T | RCBO 25Amp 1P&N 6kA C Curve 30mA Type A video.
The Hager ADC925T is a single-module RCBO rated 25A, combining overcurrent protection and 30mA residual current detection in one DIN-rail device. The ADC925T is a single pole and neutral (1P+N) unit with a 6kA breaking capacity, a C curve trip characteristic, and Type A earth leakage sensing. It complies with AS/NZS 61009 and occupies a single module on a switchboard or sub-board.
Switchboard space runs out fast when a board needs extra circuits added during a renovation or a shed wiring job. The ADC925T fits a full RCBO into a single 18mm module, so it drops into the space of one MCB without widening the board. Because both line and load terminals are non-sensitive, the unit can replace another brand without rewiring the circuit. The reduced height also leaves extra wiring space in the enclosure for a tidier board build.
For contractors populating a board, the ADC925T saves time on every pole. The factory-fitted neutral fly lead means one less conductor to land, and the built-in fault trip indicator shows whether a trip came from an overload or an earth fault. Insulation resistance testing runs faster because outgoing conductors stay connected. Stocking one slimline RCBO that replaces a standard MCB also simplifies the van and the board layout.
The ADC925T is a Type A RCBO and is not rated for smooth DC fault current from loads such as some three-phase EV chargers and variable speed drives. It is a DIN-rail device for enclosed switchboards and is not suitable for direct outdoor or exposed mounting without a rated enclosure. Its 30mA sensitivity is not the 10mA level specified for cardiac-protected patient areas.
Verified Sparky Direct customer reviews: HAGER ADC925T | RCBO 25Amp 1P&N 6kA C Curve 30mA Type A (ADC925T)
"preinstalled neutral tail makes installation quick and easy" — Peter
"Easy to fit in the board" — Victor
"gives an indication if the trip was over current or earth leakage" — Omar
(ADC925T)
The Hager ADC925T is certified to AS/NZS 61009, the combined standard for RCBOs. It provides Type A residual current detection at 30mA, the sensitivity the AS/NZS 3000 wiring rules call for on circuits feeding electronic equipment. Installation must follow the wiring rules and be carried out by a licensed electrician.
Installation must be carried out by a licensed electrician. The RCBO clips onto a standard DIN rail and takes a single 18mm module. A factory-fitted 1 metre neutral fly lead connects to the neutral bar, leaving the active and load terminals to land in the board.
The 1P+N rating means the device switches both the active and the neutral of a single-phase circuit. Full isolation suits switched-neutral applications such as caravans, construction boards, solar, and EV charging. The active pole carries the 25A overcurrent protection, and both poles open on a fault.
The compact single-module body takes the space of one MCB, so it can replace a circuit breaker to add RCD protection. Because the line and load terminals are non-sensitive, no rewiring of the circuit is needed when swapping from another brand. Confirm busbar and enclosure fit before installing.
The bi-connect terminals accept supply from either a cable in the terminal cage or a fork busbar in the slot. Single-phase and three-phase Hager fork busbars suit a board populated with these single-module RCBOs. The bi-stable DIN clip lets one unit be removed without disturbing the others on the busbar.
The warranty runs one year for domestic use and one year for commercial use, starting from the invoice date, handled as return to Sparky Direct. Warranties are void if the product is not installed by a licensed electrician. Keep proof of purchase to support any claim.
A Type A device detects AC and pulsating DC residual current, which covers most domestic and light commercial circuits. It does not detect smooth DC fault current, so loads that can produce it, such as some three-phase EV chargers and variable speed drives, need a Type B RCD. Check the load type against AS/NZS 3000.
The Hager ADC925T is available online from Sparky Direct, with Australia-wide delivery to any state or territory including regional areas. Sparky Direct is an Australian electrical wholesaler established in 2005, supplying more than 500,000 customers with transparent trade pricing.
100-Day Fuss-Free Returns
We want you to love what you buy—but if you change your mind, that’s okay too. That’s why Sparky Direct offers a 100-day money-back guarantee.
If your item isn’t in its original condition, please contact us before returning it—we might save you time and money.
All products come with a manufacturer’s or supplier’s warranty
Damaged or Faulty Goods
If your order arrives damaged or is faulty, let us know within 24 hours.
Contact us via our chat to arrange the return.
Exclusions
We can’t accept returns for:
How to Request a Return
Warranty starts from Invoice Date
Domestic Use: 1 Year
Commercial Use: 1 Year
Warranty Method: Return to Sparky Direct
These specifications and characteristics outline physical, mechanical, electrical details.
| Brand | Hager Electrical |
| SKU | ADC925T |
| Model # | ADC925T |
| Barcode # | 3250611033370 |
| Package Weight | 0.175kg |
| TYPE | VALUE |
|---|---|
| Type | Circuit Protection |
| Brand | Hager Electrical |
| Rated Current (A) | 25 |
| Height (mm) | 85 |
| Width (mm) | 18 |
| Depth (mm) | 77 |
| Standards | AS/NZ 61009-1 |
| Mounting | DIN Rail |
| Curve | C |
| Voltage (V) | 240V |
| Earth Leakage Protection Class | Type A |
| Earth Leakage Sensitivity | 30mA |
| Box increments (This item is sold individually) | 54 |
| Residual Current | 30mA |
| Breaking Capacity | 6kA |
| Overcurrent trip characteristic | C Curve |
| Earth Fault Wave Form | Type A |
| IP Rating | IP20 ( IP40 Enclosed ) |
| Number of Poles | 1P+N |
Electrical and HVAC products sold by Sparky Direct are intended for installation by licensed and appropriately qualified professionals in accordance with applicable Australian Standards and regulatory requirements. Customers are responsible for ensuring that any product purchased, including any related or associated components, is compatible and suitable for their intended installation and application.
Sparky Direct does not provide installation advice and does not assess product suitability for individual circumstances unless expressly confirmed in writing. Customers must confirm correct product selection, compatibility, compliance, and suitability with a licensed or appropriately qualified professional prior to purchase.
Tools sold by Sparky Direct must be used safely and in accordance with the manufacturer’s instructions. Customers are responsible for ensuring they have the necessary knowledge and competence to operate any tool purchased. If you are unsure how to safely or correctly use a tool, do not use it and seek guidance from the manufacturer or a suitably qualified professional.
Nothing in this clause limits or excludes any rights or guarantees available under the Australian Consumer Law.
For website terms and conditions https://www.sparkydirect.com.au/terms-of-use