The NLS CHANGEOVER-KIT is a three-piece generator changeover kit for single-phase switchboards, rated 15A at 240V. The CHANGEOVER-KIT contains one 15A IP66 appliance inlet, one 16A Type A RCBO and one 63A two-pole changeover switch. The 15A inlet sets the capacity of the kit, so generator load is limited to 15A regardless of the 63A switch rating.
Extension leads from a portable generator reach a few appliances and leave the rest of the switchboard dead. A changeover switch connects the generator at the board and isolates the mains supply. The 63A switch carries a centre-off position that breaks both supplies for servicing. The kit lands the generator lead on a fixed IP66 external inlet and puts 30mA Type A protection on the circuit.
The CHANGEOVER-KIT is a single-phase kit and is not suitable for three-phase installations. The 16A RCBO and 63A changeover switch are IP20 and are not rated for outdoor mounting, so both sit inside a switchboard or enclosure. Generator load through the kit is limited to the 15A inlet, not the 63A rating of the switch.
(CHANGEOVER-KIT)
The 15A appliance inlet sets the limit, and 15A at 240V works out to roughly 3.6kW. The 63A rating belongs to the changeover switch, not the inlet, so a larger generator does not increase what the kit will carry.
Installation must be carried out by a licensed electrician to AS/NZS 3000. The changeover switch and RCBO mount on DIN rail inside the switchboard. The appliance inlet is surface mounted and wired back to the board. Warranty on all three items is void if not installed by a licensed electrician.
The appliance inlet complies with AS/NZS 60320.1. The 16A RCBO complies with AS/NZS 61009.1. The 63A changeover switch complies with AS/NZS 60947-3. Each standard covers that item only, so the installation itself is assessed against AS/NZS 3000.
Yes. The 16A RCBO provides 30mA earth leakage protection with a Type A characteristic, which detects AC and pulsating DC residual current. It also provides overload and short circuit protection in the same 18mm module, with a C tripping curve and 4.5kA breaking capacity.
No. The 63A changeover switch is a two pole single-phase device rated 230V AC. For a three-phase changeover, NLS supplies the 30885 four pole switch instead. The 15A inlet and 16A RCBO are also single-phase only.
No. Both are IP20, which means indoor switchboard or enclosure mounting only. The 15A appliance inlet is the outdoor rated item at IP66, dust tight and protected against high pressure water jets, so it suits an external wall.
Warranty runs per item. The 16A RCBO and 63A changeover switch carry three years from invoice date. The 15A appliance inlet carries one year from invoice date. All three are return to Sparky Direct, and warranty is void if the item is not installed by a licensed electrician.
The NLS STORM-BUNDLE is available online from Sparky Direct, with Australia-wide delivery to any state or territory including regional areas. Sparky Direct is an Australian electrical wholesaler established in 2005, supplying more than 500,000 customers with transparent trade pricing.
100-Day Fuss-Free Returns
We want you to love what you buy—but if you change your mind, that’s okay too. That’s why Sparky Direct offers a 100-day money-back guarantee.
If your item isn’t in its original condition, please contact us before returning it—we might save you time and money.
All products come with a manufacturer’s or supplier’s warranty
Damaged or Faulty Goods
If your order arrives damaged or is faulty, let us know within 24 hours.
Contact us via our chat to arrange the return.
Exclusions
We can’t accept returns for:
How to Request a Return
These specifications and characteristics outline physical, mechanical, electrical details.
| Brand | NATIONAL LIGHT SOURCES |
| SKU | CHANGEOVER-KIT |
| Package Weight | 0.895kg |
| TYPE | VALUE |
|---|---|
| Type | Circuit Protection |
| Brand | National Light Sources |
| Earth Leakage Sensitivity | 30 |
| Earth Leakage Protection Class | Type A |
Electrical and HVAC products sold by Sparky Direct are intended for installation by licensed and appropriately qualified professionals in accordance with applicable Australian Standards and regulatory requirements. Customers are responsible for ensuring that any product purchased, including any related or associated components, is compatible and suitable for their intended installation and application.
Sparky Direct does not provide installation advice and does not assess product suitability for individual circumstances unless expressly confirmed in writing. Customers must confirm correct product selection, compatibility, compliance, and suitability with a licensed or appropriately qualified professional prior to purchase.
Tools sold by Sparky Direct must be used safely and in accordance with the manufacturer’s instructions. Customers are responsible for ensuring they have the necessary knowledge and competence to operate any tool purchased. If you are unsure how to safely or correctly use a tool, do not use it and seek guidance from the manufacturer or a suitably qualified professional.
Nothing in this clause limits or excludes any rights or guarantees available under the Australian Consumer Law.
For website terms and conditions https://www.sparkydirect.com.au/terms-of-use
Help other Sparky Direct users shop smarter by writing reviews for products you have purchased.